We recommand the following configuration tips when you try to configure the Smartmaster Pro with Alfen EVE Double Charger
- TIP 1: The serial number to be used in the smartmaster can be found in the paper documents supplied or the identification label on the underside of your charging station.
- TIP 2: ACE Devices installer => static load balancing must be selected.
- TIP 3: ACE Devices installer => Back office URL => SmartMaster IP ( ws://X.X.X.X:8834/ocpp).
- TIP 4: Check the device’s IP, It’s must be in the same network as the SmartMaster.
- TIP 5: ACE Devices installer => connectivity=>Meter value=>meter value sample interval = 60S
- Tip 6: ACE Devices installer => connectivity=>Meter value=>meter values sampled data =
- Sampled data 1 = Energy.Active.Import. register
- Sampled data 2 = Current.Import
- Sampled data 1 = Current.Offered